Last reviewed: November 2026. Only EPA Section 608 certified technicians may handle refrigerant. Do not attempt to add refrigerant yourself.
A refrigeration system is sealed. If it needs refrigerant, it has a leak. “Topping up” without finding the leak just wastes money and refrigerant.
Signs of a leak
- Cooling gets slowly weaker over days or weeks
- The compressor runs longer and longer
- Ice forming in odd places on the coil or lines
- Oily residue on tubing, joints or valves (refrigerant carries oil)
- A hissing sound near the lines
- A technician has had to add refrigerant more than once
Common causes
- Vibration that rubs tubing against metal
- Corrosion on coils, especially outdoors or near the coast
- Loose fittings, valve cores or service caps
- Physical damage, for example someone chipping ice off the coil
- Old brazed joints
How technicians find leaks
Electronic leak detectors, bubble solutions, UV dye and pressure tests with nitrogen are common methods. Small leaks can take time to find.
What the rules say
- Under EPA Section 608 rules, technicians who work on refrigerant circuits must be certified, and venting refrigerant is prohibited.
- Since January 1, 2026, EPA’s AIM Act leak repair rules (40 CFR 84.106) apply to appliances with a full charge of 15 pounds or more of an HFC refrigerant, or an HFC substitute with a GWP above 53. For commercial refrigeration, leaks must be repaired when the calculated leak rate exceeds 20% per year. The older Section 608 threshold of 50 pounds still applies to systems using only ozone-depleting refrigerants. Ask your technician for your system’s full charge and whether it is covered.
- Some states, including California, have their own refrigerant management rules.
Repair or replace?
If an older system using a phased-down refrigerant such as R-404A keeps leaking, compare repeated repairs with a new system using a current refrigerant. See Walk-In Refrigerants Explained and Repair or Replace.
Sources
- EPA: Section 608 of the Clean Air Act
- EPA: Stationary refrigeration leak repair requirements
- EPA: Section 608 technician certification
- CARB: Refrigerant Management Program
- EPA: Technology Transitions HFC restrictions by sector
- EPA: AIM Act leak repair requirements fact sheet (January 2026)
- 40 CFR 84.106: Leak repair