Last reviewed: November 2026. Electrical and refrigeration work should be done by a qualified technician.
The fans in the evaporator move cold air around the box. They run almost all the time, so their efficiency matters a lot, and every watt they use also becomes heat that the refrigeration must remove.
Two motor types
| Shaded-pole | ECM (electronically commutated) | |
|---|---|---|
| Technology | Older, simple induction motor | Brushless DC motor with built-in electronics |
| Efficiency | Low | Much higher: in one manufacturer comparison, a 9-watt-output ECM drew 17.7 W versus 51.8 W for a shaded-pole motor |
| Heat added to the box | More | Less |
| Speed control | Limited | Can run at variable speeds |
| Price | Cheaper | Higher |
The rules
Under 10 CFR 431.306(a)(5), evaporator fan motors in walk-ins that are under 1 horsepower and less than 460 volts must be electronically commutated or 3-phase motors. Condenser fan motors have a separate list of allowed motor types under (a)(6). Older walk-ins may still have shaded-pole motors.
Fan controls save more
- When the compressor is off, the fans do not need full speed.
- Fan controllers slow or cycle the fans during those periods while keeping enough air movement.
- Combined with ECMs, savings can be significant, and some utilities offer rebates for ECM retrofits. See Walk-In Rebates.
Signs of fan trouble
- Grinding or squealing. See Strange Noises
- Uneven temperatures in the box
- Ice forming on the coil
- A fan not spinning, or spinning slowly
A failed fan can cause the whole box to warm. Replace it promptly with the right size, rotation and voltage.
Related: Evaporators and Condensing Units and How Much Electricity Does a Walk-In Use?