Walk-In Refrigerants Explained: R-404A, R-448A, R-449A, R-290, CO2 and More

Last reviewed: November 2026. EPA rules were revised in May 2026 and are being challenged in court. Check EPA’s Technology Transitions pages before buying.

The refrigerant is the fluid that carries heat out of the walk-in. For years most walk-ins used R-404A. That is changing because of US rules on hydrofluorocarbons (HFCs) with a high global warming potential (GWP).

Common walk-in refrigerants

RefrigerantApprox. GWPWhere you see itNotes
R-404Aabout 3,900Older coolers and freezersBeing phased out of new systems; servicing existing systems is still allowed
R-448A / R-449Aabout 1,300–1,400Common replacements and new remote systemsFit under EPA’s 1,400 interim GWP limit for retail food remote condensing units from July 27, 2026; stricter limits by charge size follow from January 1, 2032
R-454C, R-455A and similarabout 150 or lessNewer low-GWP systemsMildly flammable (A2L); need equipment and practices designed for them
R-290 (propane)about 3Self-contained units and small systemsFlammable (A3); small charge limits and special safety rules
R-744 (CO2)1Supermarkets and some larger systemsVery high pressures; specialized equipment and technicians

GWP figures are approximate and vary slightly by source.

What the rules say (in short)

  • Under the AIM Act, EPA limits the GWP of refrigerants in new systems.
  • After the May 2026 revision, remote condensing unit systems, which cover many restaurant walk-ins, have an interim limit of 1,400 GWP, tightening from 2032.
  • Self-contained walk-in systems remain under a 150 GWP limit.
  • Existing systems can usually keep running and be serviced, but supplies of older refrigerants are shrinking, so prices tend to rise.

Some states are stricter than the EPA. New York has banned R-448A in most new systems since January 1, 2026, and California and Washington require GWP under 150 for new systems over 50 lb. See our state-by-state refrigerant guide.

What this means for you

  • Buying new: ask which refrigerant the system uses and confirm it is allowed for that type of system in your state today.
  • Owning an R-404A system: fix leaks promptly. When the system needs major work, compare repair against a new system with a current refrigerant.
  • Flammable refrigerants: use technicians trained for A2L or A3 refrigerants, and follow the manufacturer’s installation rules.
  • Technicians: anyone who handles refrigerants must hold EPA Section 608 certification.

Related: Walk-In Refrigerant Rules by State, Walk-In Certifications and Evaporators and Condensing Units.

Sources